DirectVent Pro Installation Guide
DirectVent Pro by Simpson Duravent is a unitized, coaxial venting system designed for use with
direct vent gas or propane stoves, heaters, and fireplaces. DirectVent
Pro features
tight inner connections for superb
performance, with no gaskets or
sealants required (unless specified by
the appliance manufacturer). All black
pipe lengths, pipe extensions, and
elbows feature laser-welded outer wall
seams for a sleek finish. Low-profile locks
and no hems or beads allow for a beautiful
product that looks elegant in any
interior.
DirectVent Pro, in combination with the
gas appliance, has been tested and
listed as a decorative gas appliance system
or as a direct vent heater system by
a major testing agency, such as UL, CSA,
Warnock Hersey, or OMNI.

Refer to the Typical Installation drawings below to select
the appropriate component parts for your installation.
- Engineered Excellence with innovation and style...DirectVent Pro.
Simpson Dura-Vent's direct vent is specified exclusively by nearly every
major stove and fireplace manufacturer in the U.S. and Canada, with the
largest choice of termination caps for direct vent available.
- All DirectVent Pro components are compatible with DirectVent GS stock,
except for the DirectVent Pro Pipe Extensions.
- Be fire safe! Use proper support and bracing. Follow local building codes and have your venting
system inspected.
|
|
*
Click on the link under the installation key (above) to be taken to the
appropriate section.
 
 
Planning Your Installation
-
For vertical gas stove installations, measure the height from the stove outlet to the ceiling to determine
the length of black pipe required. Select a ceiling support/wall thimble cover or a cathedral ceiling
support box.
-
TTo determine the length of galvanized pipe required, measure the ceiling thickness and the vertical rise in an attic or second story. Firestops are required at each floor level beyond the first floor ceiling support/wall thimble cover or cathedral ceiling support box. If an offset is required to avoid obstructions, use a pair of 45° elbows. For proper support, use elbow straps with offsets. Use wall straps for long vertical runs. Attic Insulation Shield is required in attic.
-
Measure the roof pitch. Select the proper flashing and storm collar. Determine the minimum height
above the roof.
-
For horizontal installations, check the appliance manufacturer�s instructions for minimum rise
and maximum horizontal run. A snorkel termination may be used if height restrictions prevent
adequate rise above the appliance. Select the appropriate Horizontal Termination Cap (see appliance
manufacturer installation instructions). To protect vinyl siding, select vinyl siding standoff. Check
appliance manufacturer�s instructions for wall thimble and firestop requirements.
Design Recommendation
The following design recommendations are intended as only a general
guideline to assist in the design and selection of venting components for your installation. Always read and follow Simpson
Dura-Vent Installation instructions enclosed with the cap or support box before installing
your chimney system. Installation instructions can be viewed on the item page on
our website.
Important: Check the manufacturer's rating plate and instruction manual to
confirm that the Simpson Dura-Vent direct vent system is approved for use on the brand name appliance you have selected.
-
The inner and outer pipe diameters should match the outlet size of
the appliance.
-
Check the appliance manufacturer's installation instructions to confirm
which types of vent configurations are permitted (i.e. horizontal, vertical,
chimney reline, etc.). Also, check for any venting restrictions such as maximum
horizontal run, minimum and maximum vertical rise, maximum offset, etc.
-
Be fire safe! Maintain at least the minimum clearances (air-space) between
the vent pipe and nearby combustibles, as specified in the appliance manufacturer's installation instructions. Use proper support and bracing.
Follow local building codes and have your venting system inspected.
Vent Termination Chart
|

|
|
Roof Pitch |
Minimum Height |
| Feet |
Meters |
| Flat to 7/12 |
1 |
0.30 |
| Over 7/12 to 8/12 |
1.5 |
0.46 |
| Over 8/12 to 9/12 |
2 |
0.61 |
| Over 9/12 to 10/12 |
2.5 |
0.76 |
| Over 10/12 to 11/12 |
3.25 |
0.99 |
| Over 11/12 to 12/12 |
4 |
1.22 |
| Over 12/12 to 14/12 |
5 |
1.52 |
|
|